Wire Size Calculator
Recommended AWG
—
Actual Voltage Drop
—
Voltage Drop (%)
—
Understanding Wire Sizing: AWG Gauge, Ampacity, and Voltage Drop
Wire sizing determines how much current a conductor can safely carry without overheating and how much voltage drops over a given distance. The American Wire Gauge (AWG) system assigns smaller numbers to larger wires: 14 AWG is standard for 15-amp residential circuits, 12 AWG for 20-amp circuits, 10 AWG for 30-amp circuits, and 6 AWG for 50-amp circuits like ranges and ovens. This calculator determines the appropriate wire gauge based on your circuit amperage, run length, voltage, and acceptable voltage drop percentage. Both factors -- ampacity and voltage drop -- must be satisfied, and the one requiring the larger wire governs the final selection.
Voltage drop is the loss of electrical pressure as current travels through a conductor. Every wire has resistance, and as current flows through that resistance, some voltage is consumed as heat rather than delivered to the load. The formula is: voltage drop = (2 x length x current x resistivity) / circular mil area. The factor of 2 accounts for the round-trip distance (the current must travel to the load and return). The National Electrical Code (NEC) recommends keeping voltage drop under 3% for branch circuits and 5% for the total system (feeder plus branch combined). These are recommendations, not code requirements, but exceeding them can cause operational problems.
NEC Ampacity Requirements and Table 310.16
The NEC ampacity tables (primarily Table 310.16 for conductors in raceways and cables) specify the maximum continuous current each wire size can carry based on insulation temperature rating and installation method. The three common insulation ratings are 60 degrees C (TW), 75 degrees C (THW, THWN), and 90 degrees C (THHN, THWN-2). Higher temperature ratings allow greater ampacity for the same wire size, but terminations (circuit breakers, outlets, and switches) in residential applications are typically rated for 60 or 75 degrees C, which limits the usable ampacity to those columns regardless of the wire insulation rating.
| AWG Size | Copper 60C (amps) | Copper 75C (amps) | Aluminum 75C (amps) | Typical Use |
|---|---|---|---|---|
| 14 | 15 | 15 | — | Lighting circuits |
| 12 | 20 | 20 | 15 | General outlets, kitchen |
| 10 | 30 | 30 | 25 | Dryers, water heaters |
| 8 | 40 | 50 | 40 | Ranges (small), A/C |
| 6 | 55 | 65 | 50 | Ranges, ovens, A/C |
| 4 | 70 | 85 | 65 | Feeders, sub-panels |
| 2 | 95 | 115 | 90 | Sub-panel feeders |
| 1/0 | 125 | 150 | 120 | 100A service, sub-panels |
| 4/0 | 195 | 230 | 180 | 200A service entrance |
Copper vs. Aluminum Wire: Cost, Performance, and Safety
Copper has been the standard conductor material for electrical wiring because of its excellent conductivity, ductility, and resistance to corrosion. It carries more current per gauge size than aluminum and creates reliable terminations without special compounds. However, copper prices have increased substantially, making aluminum an attractive alternative for larger wire sizes. As a general rule, aluminum wire must be one to two gauge sizes larger than copper to carry the same current: where 6 AWG copper handles 55 amps (60C rating), you need 4 AWG aluminum for the same capacity.
Aluminum wiring requires anti-oxidant compound (also called penetrox or no-ox) on all terminations to prevent aluminum oxide from forming, which creates high-resistance connections that can overheat. All connectors, breakers, and devices must be rated for aluminum (marked AL-CU or CO/ALR). Modern aluminum alloy conductors (AA-8000 series) have largely resolved the brittleness and creep issues that plagued the solid aluminum branch circuit wiring used in the 1960s and 1970s. Today, aluminum is commonly used for service entrance cables, feeder circuits to sub-panels, and large branch circuits (4 AWG and larger) where the cost savings are significant.
Conduit Fill, Derating, and Special Installations
When running wire through conduit with multiple current-carrying conductors, the NEC requires ampacity derating because conductors in a shared space generate heat that cannot dissipate as effectively. For 4 to 6 current-carrying conductors in a conduit, the ampacity is reduced to 80% of the table value. For 7 to 9 conductors, it drops to 70%. Neutral conductors that carry only unbalanced current are generally not counted, but in circuits with harmonic loads (such as LED drivers and computer power supplies), the neutral may carry significant current and must be counted. Conduit fill limits also apply: one conductor may fill 53% of the conduit area, two conductors 31%, and three or more conductors 40%.
Underground installations have different considerations. Direct-buried cable (type UF or USE) must be buried at minimum depths specified by the NEC: 24 inches for UF cable, 18 inches for rigid metal conduit, and 12 inches for PVC conduit with THWN wire under certain conditions. Underground wire runs typically face the worst-case scenario for voltage drop because of the distances involved -- a detached garage 150 feet from the main panel running a 30-amp circuit at 240V needs at least 8 AWG copper or 6 AWG aluminum to maintain acceptable voltage drop, even though 10 AWG copper has sufficient ampacity for 30 amps.
This calculator is for informational purposes only and does not constitute financial, tax, or legal advice. Always consult a qualified professional for decisions specific to your situation.
Frequently Asked Questions
What wire size do I need for a 20 amp circuit?
For a 20-amp circuit, the NEC requires a minimum of 12 AWG copper wire for runs up to about 50 feet at 120V with 3% voltage drop. For longer runs, you may need to upsize to 10 AWG. At 240V, 12 AWG copper handles 20 amps for runs up to approximately 100 feet. Always check voltage drop for your specific distance, as ampacity alone does not guarantee adequate performance on longer runs. Use this calculator to verify the exact wire size by entering your circuit amperage, distance, and voltage.
What is the difference between copper and aluminum wire?
Copper wire has lower resistance and higher ampacity per gauge size, making it the standard for branch circuits (14 AWG through 10 AWG). Aluminum wire is lighter and less expensive per foot, commonly used for larger feeders and service entrance cables (4 AWG and larger). Aluminum requires one to two gauge sizes larger than copper for the same ampacity -- for example, where 6 AWG copper is rated for 55 amps, you need 4 AWG aluminum for the same rating. Aluminum also requires special anti-oxidant compound and compatible connectors to prevent corrosion at terminations.
Why does voltage drop matter in electrical circuits?
Voltage drop reduces the electrical pressure available at the end of a circuit. The NEC recommends no more than 3% voltage drop for branch circuits and 5% total for feeder plus branch combined. Excessive voltage drop causes lights to dim, motors to run hot and inefficiently, and sensitive electronics to malfunction. A 120V circuit with 5% voltage drop delivers only 114V at the outlet, which is below the acceptable range for many appliances. For long outdoor runs to detached buildings, voltage drop is often the governing factor rather than ampacity.
What does AWG mean and how does the numbering work?
AWG stands for American Wire Gauge, the standard wire sizing system used in North America. The numbering is inverse to wire diameter: smaller numbers mean larger wires. Each decrease of 3 gauge numbers roughly doubles the cross-sectional area. Common residential sizes include 14 AWG (15-amp circuits), 12 AWG (20-amp), 10 AWG (30-amp), 8 AWG (40-amp), and 6 AWG (50-amp). Sizes larger than 1 AWG use a 0-based system: 1/0 (one-ought), 2/0, 3/0, and 4/0. The system is defined by NFPA 70 (NEC).
What wire size do I need for a 50 amp circuit?
A 50-amp circuit requires a minimum of 6 AWG copper wire per NEC Table 310.16 (60 degrees C column). This size works for runs up to approximately 55 feet at 240V with 3% voltage drop. For longer runs, upsize to 4 AWG copper. Common 50-amp applications include electric ranges, ovens, and EV chargers. If using aluminum wire, you need 4 AWG aluminum for 50 amps. Always use a double-pole 50-amp breaker with the appropriate NEMA 14-50 or 6-50 receptacle for the specific application.
How do I calculate wire size for a detached garage or shed?
For a detached building, determine the total amperage needed (typically 30-60 amps for a garage with lights, outlets, and a few power tools). Measure the one-way distance from the main panel to the sub-panel location. Enter these values into this calculator with your voltage (usually 240V for sub-panels) and 3% maximum voltage drop. For example, a 40-amp sub-panel at 100 feet from the main panel at 240V needs 6 AWG copper or 4 AWG aluminum wire. Direct-buried cable must be installed at depths specified by the NEC: 24 inches for UF cable and 18 inches for rigid metal conduit. Use our Cable Size Calculator for metric sizing.